omron — Extended Function Mode

Appendix-1 Parameter List Appendix * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. App-13 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Multi-function output setting C021 Multi-function output terminal P1 selection 00: RUN (signal during RUN) 01: FA1 (constant speed arrival signal) 02: FA2 (over set frequency arrival signal) 03: OL (overload warning) 04: OD (excessive PID deviation) 05: AL (alarm output) 06: Dc (disconnection detected) 07: FBV (PID FB status output) 08: NDc (network error) 09: LOG(logic operation output) 10:

ODc(communication option disconnected) 00 No  C022 Multi-function output terminal P2 selection 01 C026 Relay output (MA, MB) function selection 05 C028 AM selection 00: Output frequency 01: Output current 00 No  C031 Multi-function output terminal P1 contact selection 00: NO contact at MA; NC contact at MB 01: NC contact at MA; NO contact at MB 00 No  C032 Multi-function output terminal P2 contact selection 00 C036 Relay output (MA, MB) contact selection 01 Level output status setting C041 Overload warning level 0.0:

Does not operate 0.1 × Rated current to 2.0 × Rated current Rated current No A C241 *2nd overload warning level Rated current C042 Arrival frequency during acceleration 0.0 to 400.0 0.0 No Hz C043 Arrival frequency during deceleration 0.0 to 400.0 0.0 No Hz C044 PID deviation excessive level 0.0 to 100.0 3.0 No % C052 PID FB upper limit 0.0 to 100.0 100 No % C053 PID FB lower limit 0.0