2-3 Wiring *1. By factory default, multi-function output terminals, [P1] and [P2] are set to NO contact. To switch to NC contact, change the C031 and C032 settings. In addition, these terminals are reset to NO contact when initialized. *2.The factory default setting (C036) of the relay output terminals (MA, MB-MC) is set to NC contact. In addition, these terminals are reset to NC contact when initialized. To use the Inverter as an alternative to a conventional model or for built-in use with a system, check the contact logic of the relay output terminal setting (C036), and match the logic with that of the peripheral circuit before use.
If these contact logics conflict with each other, a system breakdown may occur. *3. Output terminal status 2 Design *4. Contact specifications 2-27 C036 set value Power supply Output signal Output terminal status MA-MC MB-MC 00 ON ON Closed Open OFF Open Closed OFF Open Closed 01 (Factory default) ON ON Open Closed OFF Closed Open OFF Open Closed Output terminal Resistance load Inductive load MA-MC Max. 250 V AC, 2 A 30 V DC, 3 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max. 250 V AC, 1 A 30 V DC, 1 A 250 V AC, 0.2 A 30 V DC, 0.2 A Min. 100 V AC, 10 mA 5 V DC, 100 mA