omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. 3-23 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Characteristics, Torque boost A042 Manual torque boost voltage 0.0 to 20.0 5.0 Yes % 4-11 A242 *2nd manual torque boost voltage 0.0 A043 Manual torque boost frequency 0.0 to 50.0 3.0 Yes % 4-11 A243 *2nd manual torque boost frequency 0.0 A044 V/f characteristics selection 00: Constant torque characteristics (VC) 01: Special reduced torque characteristics (Special VP) 02:

Intelligent sensor-less vector control (iSLV) 02 No  4-12 A244 *2nd V/f characteristics selection 00 A045 Output voltage gain 20. to 100. 100. Yes % 4-12 4-34 4-63 A245 *2nd output voltage gain 100. 4-12 A046 Automatic torque boost voltage compensation gain 0. to 255. 100. Yes % 4-13 A246 *2nd automatic torque boost voltage compensation gain 100. A047 Automatic torque boost slip compensation gain 0. to 255. 100. Yes % 4-13 A247 *2nd automatic torque boost slip compensation gain 100.