4-2 Function Mode RUN Command Selection Select the method for using the RUN/STOP command. 4 Functions * To switch to the 2nd RUN command, allocate 08 (SET) to the multi-function input and then turn it on. Base Frequency „ Base Frequency and Motor Voltage Match the Inverter output (frequency/voltage) to the motor rating. Be careful, especially if you set a base frequency at below 50 Hz. Otherwise, the motor may burn out. * To switch to the 2nd base frequency, allocate 08 (SET) to the multi-function input and then turn it on.
4-8 Data Frequency reference source 00 FREQ adjuster 01 Voltage or current directive from the terminal 02 F001 value set via the Digital Operator 03 ModBus communication 10 Result of the frequency operation function Parameter No. Function name Data Default setting Unit A002 RUN command selection 01: Terminal 02: Digital Operator 03: ModBus communication 02 A202 *2nd RUN command selection Related functions F004, A002, C001 to C006 Data RUN command source 01 Turn on/off the FW and RV allocated to the terminal. The STOP command is activated if both Forward/Reverse commands are input simultaneously. 02 Use the STOP/RESET key on the Digital Operator. 03 Use the ModBus communication.
Parameter No. Function name Data Default setting Unit A003 Base frequency 30 to Max. frequency [A004] 60.0 Hz A203 * 2nd base frequency 30 to Max. frequency [A204] Related functions A004, A204, A081, A082