omron — Analog Input (FV, FE, FI)

4-2 Function Mode •The frequency reference and reversibility depend on whether "16" (AT) is allocated to a multi- function input, and depend on the combination of A005 and A006, as shown below. If the frequency reference is "reversible", the motor runs in the reverse direction when "main frequency reference + auxiliary frequency reference" is less than zero, even if the FW (Forward) terminal is ON. Also, note that the motor may run in the reverse direction, resulting in prolonged acceleration time or other phenomena, if the voltage fluctuates around 0 V even with the FE terminal not connected. 4 Functions 4-13 Parameter No. Function name Data Default setting Unit A006 FE selection 00:

FE only 01: Auxiliary frequency reference of FV and FI (not reversible) 02: Auxiliary frequency reference of FV and FI (reversible) 03:

FE disabled 03  Related functions A005, A006, C001 to C008 A006 A005 AT terminal Main frequency reference Auxiliary frequency reference (FE-FC terminal) Reversibility With AT allocated to a multi-function input 00, 03 00 OFF FV-FC terminal Disabled Not reversible ON FI-FC terminal Disabled 01 OFF FV-FC terminal Disabled ON FE-FC terminal Disabled Reversible 01 00 (Example 1) OFF FV-FC terminal Enabled Not reversible ON FI-FC terminal Enabled 01 OFF FV-FC terminal Enabled ON FE-FC terminal Disabled Reversible 02 00 (Example 2) OFF FV-FC terminal Enabled Reversible ON FI-FC terminal Enabled 01 OFF FV-FC terminal Enabled ON FE-FC terminal Disabled With AT NOT allocated to a multi-function input 00   FE-FC terminal Disabled Reversible 01   Addition of the FV-FC and FI-FC terminals Enabled Not reversible 02   Addition of the FV-FC and FI-FC terminals Enabled Reversible 03   Addition of the FV-FC and FI-FC terminals Disabled Not reversible