4-2 Function Mode FV/FI/FE inputs Max (100%) Hysteresis width (b062, b065, b068) Window comparator upper limit level (b061/b064/b067) Analog operating level on disconnection (b070/b071/b072) Window comparator lower limit level (b060/b063/b066) 4 Min (O/OI: 0%) (O2 : -100%) Functions WCFV/WCFI/WCFE FVDc/FIDc/FEDc Starting Frequency •Set the frequency for starting Inverter output when the RUN signal is turned on. •Use mainly to adjust the starting torque. •With starting frequency b082 set high, the starting current increases, possibly causing the current to exceed the overload limit and overcurrent protection to work to trip the Inverter. •If "04" (OSLV:
0-Hz sensorless vector control) or "05" (V2: sensor vector control) is selected in control method selection A044, this function is disabled. 4-64 Analog application value Analog input value Parameter No. Function name Data Default setting Unit b082 Starting frequency 0.10 to 9.99 0.50 Hz FW b082 Output frequency Output voltage