4-2 Function Mode Parameter Initialization •You can initialize the rewritten set values and reset to the factory default. •You can clear trip data. •You cannot clear the P100 to P131 set values, RUN time, or power ON time. 4 „ Initialization Method Functions After setting the above parameter, use the following method to initialize. (1) Press the STOP/RESET key with the Mode and Decrement keys pressed simultaneously. • Release the STOP/RESET key when the display blinks. (The display changes as shown below.) • Release the Mode and Decrement keys. 8k8k8k8 (2) Initializing 4-66 Parameter No. Function name Data Default setting Unit b084 Initialization selection 00: Clears the trip monitor 01: