omron — Input Terminal Response Time

4-2 Function Mode (These trips are caused by hardware.) 4 Multi-function Output Terminal ON Delay/OFF Delay Functions •You can set ON/OFF delay times for each output terminal. •All output signals immediately turn on/off when the specified conditions are satisfied. Depending on the selected signal, chattering may occur. In such a case, use this function to hold or delay the signal. •Set the parameters for individual output terminals (multi-function output terminals P1 to P5 and the relay output terminal: six terminals in total). For the output terminals and the corresponding parameters, refer to the table below.

Input Terminal Response Time •You can set a sampling time individually for multi-function input terminals S1 to S8 as well as the FW terminal. This helps remove chattering or other noise. •If the terminal input becomes unstable because of chattering, increase the set value. The larger the data value is, the slower the response time. A setting range of 0 to 200 is available, which corresponds to approx. 2 to 400 ms. 4-103 No.

Error code Description 1 E10.* CT error 2 E11.* CPU error 3 E14.* Grounding protection 4 E20.* Abnormal temperature due to cooling fan stop 5 E23.* Gate array communications error 6 E25.* Main circuit error Output terminal ON delay time OFF delay time P1 C130 C131 P2 C132 C133 P3 C134 C135 P4 C136 C137 P5 C138 C139 RY (AL*) C140 C141 Function code Item Data Default setting Unit C130/C132/C134/C136/ C138/C140 Output ON delay 0.0 to 100.0: Set an ON delay time. 0.0 s C131/C133/C135/C137/ C139/C141 Output OFF delay 0.0 to 100.0: Set an OFF delay time. 0.0 s Parameter No. Function name Data Default setting Unit C160 to C167 Input terminal response time 0. to 200. (× 2 ms):

Can be set in increments of 1. 1 ms C168 Input terminal response time FW