4-2 Function Mode „ MP Adjustment •Adjust the Inverter output gain according to the meter connected to the MP terminal. Analog Output AM/AMI Terminals You can monitor the output frequency and current using the AM and AMI terminals on the control circuit terminal block. The AM terminal provides 0- to 10-V analog output. The AMI terminal provides 4- to 20-mA analog output. 4 Functions „ AM/AMI Selection •Select a signal to output from the following table. *1. This output is enabled only when "SLV", "0-Hz SLV", or "V2" is selected. (Refer to "Control Method (V/f Characteristics)" (page 4-21).) 4-105 Parameter No. Function name Data Default setting Unit C105 MP gain setting 50. to 200.:
Set a gain for the MP monitor. 100. % Related functions C027, b081 Parameter No. Function name Data Default setting Unit C028/C029 AM selection/ AMI selection 00: Output frequency (0 to Max. frequency (Hz)*3) 00 01: Output current (0% to 200%) 02: Output torque *1(0% to 200%) 04: Output voltage (0% to 100%) 05: Input voltage (0% to 200%) 06: Thermal load rate (0% to 100%) 07: LAD frequency (0 to Max. frequency [Hz]) 09: Motor temperature (0°C to 200°C) (0°C output at 0°C or lower) 10: Fin temperature (0°C to 200°C) (0°C output at 0°C or lower) 11: Output torque (signed) (AM output only. 0% to 200% *1 *2) 13: Not used 14: Not used