omron — Modbus-RTU Method

4-4 Communication Function 4 Note 1: The Inverter's rated current is "1000". Note 2: If the set value is "10000" (100.0 sec) or more, the value in the second decimal place is ignored. Functions Inverter Trip Factor List 4-172 Register No. Function name Function code R/W Monitor and setting parameters Resolution 004Eh Warning monitor d090 R Warning code  004Fh to 08FFh Not used    0900h EEPROM write  W 0: Motor parameter recalculation 1: Set value storage in EEPROM Other:

Motor parameter recalculation and set value storage in EEPROM  0901h to 1000h Not used    Trip factor high-order (factor) Trip factor low-order (Inverter status) Name Code Name Code No trip factor 0 During reset 0 Overcurrent protection during constant speed 1 During stop 1 Overvoltage protection during deceleration 2 During deceleration 2 Overcurrent protection during acceleration 3 During constant speed 3 Overcurrent protection during stop 4 During acceleration 4 Overload protection 5 Operates at frequency = 0 5 Braking resistor overload protection 6 During startup 6 Overvoltage protection 7 During DB 7 EEPROM error 8 During overload limit 8 Undervoltage protection 9 During SON/FOC 9 CT error 10 CPU error 11 External trip 12 USP error 13 Grounding protection 14 Incoming overvoltage protection 15 Momentary power interruption protection 16 Power module abnormal temperature (during FAN stop) 20 Power module abnormal temperature 21 Gate array communications error 23 Input phase loss protection 24 Main circuit error 25