omron — Modbus-RTU Method

4-4 Communication Function 4 Functions 4-187 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1343h Window comparator FI lower limit level b064 R/W Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2 1 [%] 1344h Window comparator FI hysteresis width b065 R/W Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2 1 [%] 1345h Window comparator FE upper limit level b066 R/W Set an upper limit level. Setting range: -100 to 100 Lower limit:

Lower limit level + Hysteresis width × 2 1 [%] 1346h Window comparator FE lower limit level b067 R/W Set a lower limit level. Setting range: -100 to 100 Upper limit: Upper limit level - Hysteresis width × 2 1 [%] 1347h Window comparator FE hysteresis width b068 R/W Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit:

(Upper limit level - Lower limit level) × 2 1 [%] 1348h Not used    1349h Analog operation level at FV disconnection b070 R/W 0 to 100/255 (no) 1 [%] 134Ah Analog operation level at FI disconnection b071 R/W 0 to 100/255 (no) 1 [%] 134Bh Analog operation level at FE disconnection b072 R/W -100 to 100/127 (no) 1 [%] 134Ch to 1350 Not used    1351h Integrated power clear b078 R/W Clear by writing once  1352h Integrated power display gain b079 R/W 1 to 1000 1 1353h Not used    1354h Not used    1355h Starting frequency b082 R/W 10 to 999 0.01 [Hz] 1356h Carrier frequency b083 R/W 5 to 150 0.1 [kHz] 1357h Initialization selection b084 R/W 0: Clears the trip monitor 1:

Initializes data 2: Clears the trip monitor and initializes data  1358h Initialization parameter selection b085 R/W Do not change.  1359h Frequency conversion coefficient b086 R/W 1 to 999 0.1