4-4 Communication Function 4 Functions 4-196 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1460h to 1468h Not used 1469h UP/DWN selection C101 R/W 0: Does not store the frequency data 1: Stores the frequency data 146Ah Reset selection C102 R/W 0: Trip reset at power-on 1: Trip reset at power-off 2: Enabled only during trip (Reset at power-on) 3: Trip reset only 146Bh Reset frequency matching selection C103 R/W 0: 0-Hz start 1: Frequency matching start 2:
Frequency pull-in restart 146Ch Not used 146Dh MP gain setting C105 R/W 50 to 200 1 [%] 146Eh AM gain setting C106 R/W 50 to 200 1 [%] 146Fh AMI gain setting C107 R/W 50 to 200 1 [%] 1470h Not used 1471h AM bias setting C109 R/W 0 to 100 1 [%] 1472h AMI bias setting C110 R/W 0 to 100 1 [%] 1473h Overload warning level 2 C111 R/W 0 to 2000 0.1 [%] 1474h to 147Ch Not used 147Dh FV zero adjustment C121 R/W 0 to 65530 1 147Eh FI zero adjustment C122 R/W 0 to 65530 1 147Fh FE zero adjustment C123 R/W 0 to 65530 1 1480h to 1485h Not used