omron — Monitor Mode (d***)

Appendix-1 Parameter List AppAppendix Appendix-1 Parameter List Monitor Mode (d ) •The default setting displays "d001" at power-on. To select the optional display, change the setting in "b038". Appendix App-1 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Set value d001 Output frequency monitor 0.0 to 400.0  Yes Hz d002 Output current monitor 0.0 to 999.9 1000 to 9999   A d003 Rotation direction monitor F: Forward o: Stop r: Reverse    d004 PID feedback value monitor 0.00 to 99.99 100.0 to 999.9 1000. to 9999.

1000 to 9999 (10000 to 99990) 100 to 999 (100000 to 999000) (Enabled when the PID function is selected)    d005 Multi-function input monitor FW (Example) Terminals FW, S7, S2, S1 : ON Terminals S8, S6, S5, S4, S3: OFF S8 S7 S6 S5 S4 S3 S2 S1    d006 Multi-function output monitor (Example) Terminals P2, P1 : ON Terminals MA, P5, P4, P3: OFF MA P5 P4 P3 P2 P1    d007 Output frequency monitor (after conversion) 0.00 to 99.99 100.0 to 999.9 1000. to 9999. 1000 to 3996 (10000 to 39960) (Output frequency × Conversion factor of b086)  Yes  d008 Real frequency monitor -400. to -100. -99.9 to 0.00 to 99.99 100.0 to 400.0   Hz d009 Torque reference monitor -200. to +200.

  % d010 Torque bias monitor -200. to +200.   % d012 Output torque monitor -200. to +200.   % d013 Output voltage monitor 0. to 600.   V