omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-27 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Upper/Lower limit, Jump A063 Jump frequency 1 Jump frequency: 0.0 to 400.0 Jump frequency width: 0.0 to 10.0 0.00 No Hz 4-30 A064 Jump frequency width 1 0.50 A065 Jump frequency 2 0.00 A066 Jump frequency width 2 0.50 A067 Jump frequency 3 0.00 A068 Jump frequency width 3 0.50 A069 Acceleration stop frequency 0.00 to 99.99 100.0 to 400.0 0.00 No Hz A070 Acceleration stop time 0.0 to 60.0 0.0 No s PID control A071 PID selection 00:

Disabled 01: Enabled 02: Reverse output enabled 00 No  4-31 A072 PID P gain 0.2 to 5.0 1.0 Yes  A073 PID I gain 0.0 to 999.9 1000. to 3600. 1.0 Yes s A074 PID D gain 0.00 to 99.99 100.0 0.00 Yes s A075 PID scale 0.01 to 99.99 1.00 No Time A076 PID feedback selection 00: FI 01: FV 02: RS485 communication 03: Pulse train frequency 10: Operation function output 00 No  A077 Reverse PID function 00: OFF (Deviation = Target value - Feedback value) 01: ON (Deviation = Feedback value - Target value) 00 No  A078 PID output limit function 0.0 to 100.0 0.0 No % PID control A079 PID feedforward selection 00: Disabled 01: FV 02: FI 03: FE 00 No  4-31 AVR A081 AVR selection 00: Always ON 01:

Always OFF 02: OFF during deceleration 02 No  4-35 A082 AVR voltage selection 200-V class: 200/215/220/230/240 400-V class: 380/400/415/440/460/480 200/ 400 No V