Appendix A 1. For the BW500/L, P762 indexes with values shown as 0 cannot be turned on. Write Block The standard Write block is made up of the following sections: SPA, command control, multispan, PID, batch, batch prewarn, word order. If any of these sections is ‘turned off’ by setting the corresponding part of P762 to a zero, the new map will shift down accordingly and the size will be reduced by that amount.
Multiply the parameter value by the memory size, then add up the results to get the total Write Block Template for Mass Dynamic Products Page 52 SmartLinx PROFIBUS DP – INSTRUCTION MANUAL 7ML19981AQ03 SPA 8 1 1 parameter number parameter number primary index primary index secondary index secondary index returned value new value decimal place decimal place format format read/write read/ write command control 9 1 1 ------------------ command control multispan 10 1 01 ------------------ multispan selection PID 11 1 01 ------------------ PID 1 setpoint value PID 2 setpoint value batch 12 1 01 ------------------ batch setpoint value batch prewarn 13 1 01 ------------------ batch prewarn setpoint value word order 14 1 1 word order word order status 2 15 1 1 instrument status 2 ------------------- batch total 16 1 01 batch total ------------------- Name of area P762 Point value Memory size for Write block per value Result of multiplying value * memory size status 1 0 rate 2 0 load 3 0 speed 4 0 total 5 0 relay status 6 0