Siemens — Message Responses

Message Responses The BW100 response to a flow rate (MT=50) load (MT=51) or speed (MT=52) message request is in the following format. som DEVICE MT READING eom Example: Data ASCII Example Field Character Description som STX start of message DEVICE 00 from BW100 # 0 MT 50 material flow rate response READING 392.5 is 392.5 eom CR end of message Communications The response to a material total (MT=53) message request is in the following format. som DEVICE MT READING UNITS eom Example:

Data ASCII Example Field Character Description som STX start of message DEVICE 01 from BW100 # 1 MT 53 material total response READING 129.2 is 129.2 UNITS t metric tonnes eom CR end of message 7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 49