Relay/Alarm Function (P100 - P117) Note: These parameter are specific to the use of the relay/alarm function. Refer to Operation/Relay Output, page 13. P100 Relay Set Up Sets the alarm mode for the relay. Entry: 0 = off 1 = rate 2 = auto zero 3 = belt speed 4 = belt load 5 = error P101 High Alarm Sets the high alarm setpoint for relay functions P100 = 1, 3 or 4. Enter the value in % of full scale. P102 Low Alarm Parameters Sets the low alarm setpoint for relay functions P100 = 1, 3 or 4. Enter the value in % of full scale. P117 Alarm Dead Band Sets the dead band to prevent relay chatter due to fluctuations at the high or low setpoint.
Enter the value in % of full scale End of relay/alarm parameters. mA Output Parameters (P200 - P220) Note: These parameters are specific to the use of the mA output. Refer to Operation on page 42 for details. 7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 53