Siemens — General data

© Siemens 2022 Monitoring and control devices SIMOCODE 3UF motor management and control devices SIMOCODE pro 3UF7 motor management and control devices General data Control circuit 1) Measurement conditions: Room temperature; active thermistor and 2 active inputs and outputs; bus transmission rate for PROFIBUS 1.5 Mbaud, for PROFINET 100 bps; for pro C/pro S: 1 current measuring module and one operator panel with 2 active LEDs; for pro V: 1 current/voltage measuring module and one operator panel with display with 2 active LEDs.

10/12 Siemens IC 10 · 2022 Basic units Type 3UF7000-1AU00-0, 3UF7010-1AU00-0, 3UF7011-1AU00-., 3UF7020-1AU01-0, 3UF7012-1AU00-0, 3UF7013-1AU00-0 3UF7000-1AB00-0, 3UF7010-1AB00-0, 3UF7011-1AB00-., 3UF7020-0AB01-0, 3UF7012-1AB00-0, 3UF7013-1AB00-0 Rated control supply voltage Us (acc. to IEC 61131-2) 110 ... 240 V AC/DC; 50/60 Hz 24 V DC Operating range • SIMOCODE pro C (3UF7000), SIMOCODE pro V PROFIBUS (3UF7010) and SIMOCODE pro V Modbus RTU (3UF7012) • SIMOCODE pro V PROFINET (3UF7011), SIMOCODE pro V EtherNet/IP (3UF7013) and SIMOCODE pro S (3UF7020) - Operation - Startup 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us 0.85 ... 1.1 x Us 0.80 ... 1.2 × Us 0.85 ... 1.1 x Us 0.85 ...

1.2 × Us Power consumption1) • SIMOCODE pro C (3UF7000) and SIMOCODE pro S (3UF7020) • SIMOCODE pro S (3UF7020) • SIMOCODE pro V PROFIBUS (3UF7010) and SIMOCODE pro V Modbus RTU (3UF7012) • SIMOCODE pro V PROFINET (3UF7011) and SIMOCODE pro V EtherNet/IP (3UF7013) 5.3 VA/2.9 W 2.3 W 4.7 VA/2.5 W 2.1 W 8.3 VA/3.6 W 2.6 W 8.3 VA/4.8 W 3.9 W Rated insulation voltage Ui V 300 (for pollution degree 3) Rated impulse withstand voltage Uimp kV 4 Relay outputs • Number - SIMOCODE pro C, SIMOCODE pro V (incl.

SIMOCODE pro V PN GP) - SIMOCODE pro S • Specified short-circuit protection for auxiliary contacts (relay outputs) - Fuse links - Miniature circuit breakers • Rated uninterrupted current A • Rated switching capacity - AC-15 - DC-13 3 monostable relay outputs 2 monostable relay outputs 6 A operational class gG; 10 A quick-response (IEC 60947-5-1) 1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik 6 6 A/24 V AC; 6 A/120 V AC; 3 A/230 V AC 2 A/24 V DC; 0.55 A/60 V DC; 0.25 A/125 V DC Inputs (binary) 4 inputs supplied internally by the device electronics (with 24 V DC) and connected to a common potential Thermistor motor protection (binary PTC) • Summation cold resistance k • Response value k • Return value k 1.5 3.4 ...

3.8 1.5 ... 1.65 2nd-generation current/voltage measuring modules Type 3UF7..0- 1AA01-0 3UF7..1- 1AA01-0 3UF7..2- 1AA01-0 3UF7..3- 1.A01-0 3UF7..4- 1BA01-0 Main circuit Current setting Ie A 0.3 ... 4 3 ... 40 10 ... 115 20 ... 200 63 ... 630 Rated insulation voltage Ui V 690 Rated operational voltage Ue V 690 Rated impulse withstand voltage Uimp kV 6 Rated frequency Hz 50/60 Type of current Three-phase current Short circuit Additional short-circuit protection is required in the main circuit Typical voltage measuring range • Phase-to-phase voltage/line-to-line voltage (e.g. UL1 L2) V • Phase voltage (e.g. UL1 N) V 110 ... 690 65 ...

400 Accuracy at 25 °C, 50/60 Hz Valid for voltage range Valid for current range A • Voltage measurement % • Current measurement % • Temperature drift of current measurement - 3UF7110-1AA01-0 % - 3UF7111-1AA01-0, 3UF7112-1AA01-0, 3UF7113-1AA01-0, % 3UF7113-1BA01-0, 3UF7114-1BA01-0 • Power factor measurement (p.f. 0.5) % • Apparent power measurement (p.f. 0.5) % • Active power measurement (p.f. 0.5) % • Energy measurement (p.f. 0.5) % • Frequency measurement (p.f. 0.5) % • Phase-to-phase voltage UL in the range 0.85 x 110 V ... 1.1 x 690 V • Phase voltage UL in the range 0.85 x 65 V ... 1.1 x 400 V 0.25 ... 8/ 8 ... 32 2.25 ... 80/ 80 ... 320 7.5 ... 230/ 230 ... 920 15 ...

400/ 400 ... 1 600 47 ... 1 260/ 1 260 ... 5 040 1.5 1.5/3 (typical) 0.02 K 0.01 K 1.5/5 (typical) 3/5 (typical) 5/10 (typical) 5/10 (typical) 1.5 Notes on voltage measurement • Supply lines for voltage measurement In the supply lines from the main circuit for voltage measurement of SIMOCODE pro it may be necessary to provide additional line protection! 10