Delta · DRC · 10 стр.

DRC-12V60W1AZ (June 2014, Rev. 01)

Read online

Related manuals

Contents

Document text

Model Numbering

TECHNICAL DATASHEET Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55°C Power will not de-rate for the entire input voltage range Efficiency > 86.0% @ 115Vac & 230Vac NEC Class 2 / Limited Power Source (LPS) certified Overvoltage / Overcurrent / Over Temperature Protections Safety Standards CB Certified for worldwide use Model Number: DRC-12V60W1AZ Unit Weight : 0.22 kg Dimensions (L x W x D):

91 x 71 x 55.6 mm General Description The DRC-12V60W1AZ is part of the Chrome DIN Rail Power Supply series, which is designed for use in compact cabinets for home automations and the food and beverage industry. Delta’s Chrome DIN Rail Power Supply series offers double isolated input. This means that no Earth connection is required thus resulting in low leakage current. This product provides a universal input voltage range of 90-264Vac, and a wide temperature range of -25°C to 71°C. The Chrome series is certified to safety standard according to IEC/EN/UL 60950-1 Information Technology Equipment (ITE) and UL 508 Industrial Control Equipment (ICE).

The series is also fully compliant with RoHS Directive 2011/65/EU for environmental protection. NEC Class 2 and Limited Power Source (LPS) approvals are available for this product. Model Information Chrome DIN Rail Power Supply Model Number Output Curr ent DRC-12V60W1AZ 4.50A Model Numbering 1 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (June 2014, Rev. 01) Input Voltage Range Output Voltage 90-264Vac (125-375Vdc) 12Vdc DR C – 12V 60W 1 A Z DIN Rail Isolation Class II Power Supply Output Voltage Output Power (60W series model) Single Phase Chrome Series Plastic Case

Page 1

Mechanical

TECHNICAL DATASHEET Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AZ Specifications Input Ratings / Characteristics *DC input voltage is not included in the UL safety approval. Additional testing might be necessary. Output Ratings / Characteristics Mechanical 2 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (June 2014, Rev.

01) Nominal Input Voltage 100-240Vac Input Voltage Range 90-264Vac Nominal Input Frequency 50-60Hz Input Frequency Range 47-63Hz Nominal DC Input Voltage* 125-375Vdc Input Current Efficiency at 100% Load > 86.0% @ 115Vac & 230Vac Max Inrush Current (Cold Start) Leakage Current Nominal Output Voltage 12Vdc Output Voltage Tolerance ± 2% (initial set point tolerance from factory) Output Voltage Adjustment Range 11.5-14.0Vdc Output Current 4.50A Output Power 54W Line Regulation Load Regulation PARD (20MHz) 150mVpp Rise Time Start-up Time Hold-up Time > 16ms @ 115Vac, > 30ms @ 230Vac (100% load) Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 10-100% load Start-up with Capacitive Loads 3,000µF Max Case Cover Plastic Dimensions (L x W x D) 91 x 71 x 55.6 mm Unit Weight 0.22 kg Indicator Green LED (DC OK) Cooling System Convection Terminal Input 2 Pins (Rated 300V/25A) Output 4 Pins (Rated 300V/25A) Wire Input / Output AWG 24-12 Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715 Noise (1 Meter from power supply) Sound Pressure Level (SPL)

Page 2

Reliability Data

TECHNICAL DATASHEET Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AZ Environment Surrounding Air Temperature Operating -25°C to +71°C Storage -25°C to +85°C Power De-rating > 55°C de-rate power by 2.5% / °C Operating Humidity 5 to 95% RH (Non-Condensing) Operating Altitude 0 to 2,000 Meters Shock Test (Operating) IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 shocks for each 3 directions, 9 times in total Vibration (Operating) IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/SІ (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions Pollution Degree 2 Protections *PE:

Primary Earth Reliability Data 3 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (June 2014, Rev. 01) Overvoltage Overload / Overcurrent Over Temperature > 75°C Surrounding Air Temperature @ 100% load, Latch-off Mode Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) Degree of Protection IP20 Protection Against Shock Class II (No PE* connection is required) MTBF > 500,000 hrs. as per Telcordia SR-332 I/P: 100Vac, O/P: 100% load, Ta: 35°C Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C)

Page 3

EMC

TECHNICAL DATASHEET Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AZ Safety Standards / Directives EMC 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line) *Warning: This is a Class A product. In a residential, commercial or light industrial environment it may cause radio interference. This product is not intended to be installed in a residential environment; in a commercial and light industrial environment with connection to the public mains supply, the user may be required to take adequate measures to reduce interference.

4 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (June 2014, Rev. 01) Electrical Safety TUV Bauart to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS) Industrial Control Equipment UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 Class 2 Power Supply UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC Material and Parts RoHS Directive 2011/65/EU Compliant Galvanic Isolation Input to Output 3.0KVac EMC / Emissions CISPR 22, EN 55022, FCC Title 47:

Class A* Immunity to EN 55024 Electrostatic Discharge IEC 61000-4-2 Level 3 Criteria A1) Air Discharge: 8kV Contact Discharge: 4kV Radiated Field IEC 61000-4-3 Level 2 Criteria A1) 80MHz-1GHz, 3V/M with 1kHz tone / 80% modulation Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A1) 1kV Surge IEC 61000-4-5 Level 3 Criteria A1) Common Mode2): 2kV Differential Mode3): 1kV Conducted IEC 61000-4-6 Level 2 Criteria A1) 150kHz-80MHz, 3Vrms Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A1) 1A/Meter Voltage Dips IEC 61000-4-11 > 95% dip; 0.5 cycle (10ms) Voltage Fluctuation and Flicker IEC/EN 61000-3-3

Page 4