EM600 High-Performance Vector Control Inverter User Manual 1.2 EM600 Operation Status 1.2.1 Operating Status of Inverter EM600 inverter operating status: Parameter setting, normal running, JOG running, autotuning, stop, JOG stop and fault. Parameter setting status: After it is powered on and initialized and is standby without a fault or a start-up command, inverter has no output. Normal running status: Having received an active start command through keypad, control terminal or communication, inverter drives motor as per setting input. JOG running status: Drives motor at JOG input speed through setting of keypad, 11 Items Specifications multi-function inputs:
X7 can be selected as a high-speed pulse input terminal (F02.06=35/38/40); 10 numeric input terminals, X1 - X6 and X8 - X11, can be only used as common numeric input terminals. 3 (standard AI1 - AI3) analog inputs + 1 (expansion card AI4) analog input: 1 (AI1) voltage input (0 - 10 V); Analog Input Terminal 2 (AI2/AI3) voltage inputs (0 - 10 V) or current inputs (0 - 20 mA); 1 (AI4) voltage input (-10V - 10V). 2 (standard Y1/Y2) + 1 (expansion card Y3) OC multi-function outputs and 2 (R1: EA/EB/EC, R2: RA/RB/RC) relay multi-function outputs. Numeric Output Terminal Maximum output current of OC: 50 mA; relay contactor capacity: 250 VAC/3 A or 30 VDC/1 A.
When relay works, EA-EC and RA-RC are on, but EB-EC and RB-RC are off. 2 multi-functional analog output terminals (M1/M2) are with Analog Output Terminal output 0 – 10 V or 0 – 20 mA. LED LED displays relevant information about inverter. Keypad Upload and download parameter setting information of inverter Display Parameter Copy to realize rapid copy. Short circuit, overcurrent, overvoltage, undervoltage, phase loss, Protection Protection overload, overheating, overspeed, offload, external fault, etc. To be installed indoor with an altitude of less than 1,000 meters, Installation Site free from dust, corrosive gas and direct sunlight.
Ambient Temperature -10℃ - +40℃, 20% - 90% RH (no condensation) Working Vibration Condition Storage Temperature -25℃ - +65℃ Wall mounting, floor mounting (electrical cabinet) and flush Installation Method mounting Protection Grade IP20/IP21 (450Kw and above) Cooling Method Forced air cooling