User Manual of EM730/EM730E Series Inverter When the input voltage of the terminal is within [1V, 3V], its corresponding logic status will remain unchanged. Logic 1 0 0V 1V 3V Voltage Fig. 7-10 Correspondence between Analog Input Terminal Voltage and Current Logic Status If it is used as an analog input terminal, the filter time and corresponding offset curve can be set via F02.32 to F02.60. The terminals AI1 to AI2 can be set separately. 163 Function Default Function code name Parameter description Unit Attribute code setting F02.32 Options of analog input curve Ones place: Options of AI1 curve 0: curve 1 1: curve 2 2: curve 3 3: curve 4 Tens place: AI2 curve selection 0: curve 1 1:
curve 2 2: curve 3 3: curve 4 10D 〇 F02.33 Minimum input of curve 1 0.00 - F02.35 V 0.10 ● F02.34 Minimum input setting of curve 1 –100.0 - +100.0 % 0.0 ● F02.35 Maximum input of curve 1 F02.33 - 10.00 V 9.90 ● F02.36 Maximum input setting of curve 1 –100.0 - +100.0 % 100.0 ● F02.37 Minimum input of curve 2 -10.00 - F02.39 V 0.10 ● F02.38 Minimum input setting of curve 2 –100.0 - +100.0 % 0.0 ● F02.39 Maximum input of curve 2 F02.37 - 10.00 V 9.90 ● F02.40 Maximum input setting of curve 2 –100.0 - +100.0 % 100.0 ● F02.41 Minimum input of curve 3 0.00V - F02.43 V 0.10 ●