omron — Details

DEVICENET monitor command DEVICENET monitor command Syntax DEVICENET Function Used for reading DeviceNet status. Details The DEVICENET monitor command displays information about the network in the following format: Local MAC ID: 10 BAUD rate: 125 KBaud Installed MAC ID Status ---------------------- 3 Device being scanned 63 Device timed-out Packets transmitted: 1234567890 Transmission errors: 1234567890 Packets received: 1234567890 Reception overflow: 1234567890 Missed packets: 1234567890 CanBus status: message The CanBus status is given as one or more of the messages shown in the following table.

DEVICENET Status Messages—Possible Status Messages eV+Operating System Reference Guide, 2.x,18321-000 Rev A Page 72 Activity detected Bus off Bus warning Device not in device list Device idle (not being scanned) Device timed-out Device being scanned Error allocating Master/Slave connection set Error reading I/O connection 1 input size Error reading I/O connection 1 output size Error reading I/O connection 2 input size Error reading I/O connection 2 output size Error reading product code Error reading vendor id Invalid vendor id Invalid I/O connection 2 output size Invalid product code Master/Slave connection set is busy M/S connection set sync fault Online Online at 125 KBaud Online at 250 KBaud Online at 500 KBaud