omron — 6 Parameter Table

6 Parameter Table This parameter table shows the most important parameters. Default settings are bold type. Refer to the instruction manual for a complete list of parameters. 22 I67E-EN V1000 Quick Start Guide 6 Parameter Table Par. Name Description b1-03 Stopping Method Selection Selects the stopping method when the run command is removed. 0:Ramp to Stop 1:Coast to Stop 2:DC Injection Braking to Stop 3:Coast with Timer (a new run command is ignored if received before the timer expires) b1-04 Reverse Operation Selection 0:Reverse enabled 1:Reverse prohibited b1-14 Phase Order Selection Switches the output phase order.

0:Standard 1:Switch phase order DC Injection Braking b2-01 DC Injection Braking Start Fre- quency Sets the frequency at which DC Injection Braking starts when Ramp to Stop (b1-03 = 0) is selected. If b2-01 b2-02 DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the drive rated current. In OLV the DC excitation current is determined by E2-03. b2-03 DC Inj. Braking Time/DC Excitation Time at Start Sets the time of DC Injection Braking at start in units of 0.01 seconds. Disabled when set to 0.00 seconds. b2-04 DC Inj. Braking Time at Stop Sets the DC Injection Braking time at stop. Disabled when set to 0.00 seconds.

Acceleration/ Deceleration C1-01 Accel Time 1 Sets the acceleration time 1 from 0 to the max. output fre- quency. C1-02 Decel Time 1 Sets the deceleration time 2 from the max. output frequency to 0. Par. Name Description Initialization Parameters A1-01 Access Level Selection Selects which parameters are accessible via the digital opera- tor. 0:Operation only 1:User Parameters 2:Advanced Access Level A1-02 Control Method Selection Selects the Control Method of the drive. 0: V/f Control 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) Note: Not initialized with A1-03! A1-03 Initialize Parame- ters Resets all parameters to default. (returns to 0 after initial- ization) No Initialize 1110:

User Initialize (The user must first set user parameter values and then store them using parameter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization Operation Mode Selection b1-01 Frequency Reference Selection 0:Operator - d1-†† values 1:Analog input A1 or A2 2:Serial Com - RS-422/485 3:Option board 4:Pulse Input (Terminal RP) b1-02 Run Command Selection 0:Operator - RUN and STOP keys 1:Terminals - Digital Inputs 2:Serial Com - RS-422/485 3:Option board connected