B.2 Parameter Table Parameter can be changed during run. If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands. Note: Cycle power to the drive to enable MEMOBUS/Modbus settings. u L: Protection Function L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, and other types of hardware protection. Parameter List B SIEP C710606 33A OYMC AC Drive – J1000 User Manual 177 No. Name Description Range Def. Mode Addr. Hex Pg. H4: Multi-Function Analog Output AM Use H4 parameters to configure the multi-function analog output terminal AM.
H4-01 Multi-Function Analog Output Terminal AM Selects the data to be output through multi-function analog output terminal AM. Set the desired monitor parameter to the digits available in U- . For example, enter “103” for U1-03. When using this terminal in through mode or when not using it at all, set “000” or “031”. 000 to 999 102 O 41D 101 H4-02 Multi-Function Analog Output Terminal AM Gain Sets terminal AM output level when selected monitor is at 100%. Maximum output voltage is 10 V. -999.9 to 999.9 100.0% S 41E 101 H4-03 Multi-Function Analog Output Terminal AM Bias Sets terminal AM output level when selected monitor is at 0%. -999.9 to 999.9 0.0% O 41F 101 H5:
MEMOBUS/Modbus Communications Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network (communication option required). H5-01 Drive Slave Address Selects drive slave number (address) for MEMOBUS/Modbus communication. Cycle power for the setting to take effect. 0 to FF 1F O 425 191 H5-02 Comm. Speed Selection Selects the baud rate for MEMOBUS/Modbus communication. Cycle power for the setting to take effect. 0 : 1200 bps 1 : 2400 bps 2 : 4800 bps 3 : 9600 bps 4 : 19200 bps 5 : 38400 bps 0 to 5 3 O 426 191 H5-03 Comm. Parity Selection Selects the communication parity for MEMOBUS/Modbus communication. Cycle power for the setting to take effect. 0: No parity 1: Even parity 2:
Odd parity 0 to 2 0 O 427 191 H5-04 Stopping Method After Comm. Error Selects the stopping method when a communication time-out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3: Alarm only 0 to 3 3 O 428 191 H5-05 Comm. Fault Detection Selection Enables or disables the communications timeout fault (CE). 0: Disabled - A communication loss will not cause a communication fault. 1: Enabled - If communication is lost for more than 2 seconds, a CE fault will occur. 0, 1 1 O 429 191 H5-06 Drive Transmit Wait Time Set the wait time between receiving and sending data. 10 to 65 10 ms O 42A 191 H5-07 RTS Control Selection Selects "request to send" (RTS) control: 0:
Disabled - RTS is always on. 1: Enabled - RTS turns on only when sending. 0, 1 1 O 42B 191 H5-12 Run Command Method Selection 0: FWD/STOP, REV/STOP Method 1: RUN/STOP, FWD/REV Method 0, 1 0 O 43D 191 H5-13 MEMOBUS Freq. Reference and Freq. Monitor Unit 0: 0.1 Hz/1 1: o1-03 based 2: 100%/30000 3: 0.1%/1 0 to 3 0 O 43E 191 No. Name Description Range Def. Mode Addr. Hex Pg. L1: Motor Protection Functions Use L1 parameters to configure motor protective functions. L1-01 Motor Overload Protection Selection Sets the motor thermal overload protection (oL1) based on the cooling capacity of the motor. 0: Disabled 1: Standard Fan Cooled (speed range 0 to 2 1 S 480 102