B.2 Parameter Table Parameter can be changed during run. 176 SIEP C710606 33A OYMC AC Drive – J1000 User Manual H1 Multi-Function Digital Input Selections H1- Setting Function Description Page 41 Reverse Run Command (2-Wire sequence) Open: Stop Closed: Reverse run 94 61 External Search Command 1 Closed: Activates Current Detection Speed Search from the max. output frequency (E1-04) 94 62 External Search Command 2 Closed: Activates Current Detection Speed Search from the frequency reference 94 67 Communications Test Mode Tests the MEMOBUS/Modbus RS-422/485 interface. 95 No. Name Description Range Def. Mode Addr. Hex Pg. H2:
Multi-Function Digital Output MA-MB-MC Use H2 parameters to assign functions to the multi-function digital output MA-MB-MC. H2-01 Terminal MA, MB and MC Function Selection (relay) Refer to H2 Multi-Function Digital Output Settings on page 176 for a description of setting values. 0 to 13D E O 40B 95 H2 Multi-Function Digital Output Settings H2-01 Setting Function Description Page 0 During Run Closed: A Run command is active or voltage is output 95 1 Zero Speed Closed: Output frequency is 0 95 2 Speed Agree 1 Closed: Output frequency equals the speed reference (plus or minus 2 Hz hysteresis) 96 4 Frequency Detection 1 Closed:
Output frequency is less than or equal to the value in L4-01 with 2 Hz hysteresis 96 5 Frequency Detection 2 Closed: Output frequency is greater than the value in L4-01 with 2 Hz hysteresis 96 6 Drive Ready Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive mode 97 7 DC Bus Undervoltage Closed: DC bus voltage is below the Uv trip level 97 8 During Baseblock (N.O.) Closed: There is no output voltage 97 B Torque Detection 1 (N.O.) Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time set in parameter L6-03 97 E Fault Closed:
Fault occurred (other than CPF00 and CPF01) 97 F Not used Set this value when the terminal is not used, or when using the terminal in the pass-through mode 97 10 Minor Fault Closed: An alarm is triggered 97 17 Torque Detection 1 (N.C.) Open: When the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03 97 1A Reverse Direction Closed: Drive is running in the reverse direction 98 1E Restart Enabled Closed: An automatic restart is performed 98 3C LOCAL/REMOTE Status Closed: LOCAL Open: REMOTE 98 3D Speed Search Closed:
Speed search is being executed 98 100 to 102; 104 to 108; 10B, 10E, 110, 117, 11A, 11E, 13C, 13D H2 Parameter Functions Reversed Output Switching of 0 to 13D Reverse the output switching of the multi-function output functions. Set the last two digits of 1 to reverse the output signal of that specific function Examples: Setting “108” reverses the output of “During baseblock”, which is setting value 08 Setting “13C” reverses the output of “LOCAL/REMOTE Status”, which is setting “3C” 98 No. Name Description Range Def. Mode Addr. Hex Pg. H3: Analog Input A1 Use H3 parameters to set the analog input terminal A1. H3-01 Terminal A1 Signal Level Selection Sets the input level for terminal A1. 0:
0 to +10 V (lower limit) 1: 0 to +10 V (no lower limit) 2: 4 to 20 mA 3: 0 to 20 mA 0 to 3 0 O 410 98 H3-03 Terminal A1 Gain Setting Sets the level of the input value when 10 V (20 mA) is input at terminal A1. -999.9 to 999.9 100.0% O 411 99 H3-04 Terminal A1 Bias Setting Sets the level of the input value when 0 V (0 or 4 mA) is input at terminal A1. -999.9 to 999.9 0.0% O 412 99 H3-13 Analog Input Filter Time Constant Sets the primary delay filter time constant for terminal A1 or potentiometer (optional). Used for noise filtering. 0.00 to 2.00 0.03 s O 41B 101