B.2 Parameter Table u H Parameters: Multi-Function Terminals H parameters assign functions to the multi-function input and output terminals. Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization. Parameter List B SIEP C710606 33A OYMC AC Drive – J1000 User Manual 175 No. Name Description Range Def. Mode Addr. Hex Pg. H1: Multi-Function Digital Input H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F". H1-01 Multi-Function Digital Input Terminal S1 Function Selection Assigns a function to the multi-function digital inputs.
Refer to H1 Multi-Function Digital Input Selections on page 175 for a description of setting values. 1 to 67 40 O 438 90 H1-02 Multi-Function Digital Input Terminal S2 Function Selection 41 O 439 90 H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 67 24 O 400 90 H1-04 Multi-Function Digital Input Terminal S4 Function Selection 14 O 401 90 H1-05 Multi-Function Digital Input Terminal S5 Function Selection 3 (0) O 402 90 H1 Multi-Function Digital Input Selections H1- Setting Function Description Page 0 3-Wire Sequence Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence) 90 1 LOCAL/REMOTE Selection Open:
REMOTE, Run and frequency reference source set in b1-01/02 Closed: LOCAL, LED operator is run and reference source 91 2 Serial Communication Reference Selection Open: REMOTE, Run and frequency reference source set in b1-01/02 Closed: MEMOBUS/Modbus Communication 91 3 Multi-Step Speed Reference 1 Used to select Multi-Step Speeds set in d1-01 to d1-08 91 4 Multi-Step Speed Reference 2 91 5 Multi-Step Speed Reference 3 91 6 Jog Reference Selection Open: Selected speed reference Closed: Jog Frequency reference (d1-17). Jog has priority over all other reference sources. 91 7 Accel/Decel Time 1 Used to switch between Accel/Decel Time 1 and 2 91 8 Baseblock Command (N.O.) Open:
Normal operation Closed: No drive output 91 9 Baseblock Command (N.C.) Open: No drive output Closed: Normal operation 91 A Accel/Decel Ramp Hold Closed: The drive pauses during acceleration or deceleration and maintains the output frequency. 92 F Not used Select this setting when not using the terminal or when using the terminal in a pass-through mode. 92 10 Up Command Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. 92 11 Down Command 92 14 Fault Reset Closed: Resets faults if the cause is cleared and the Run command is removed.
93 15 Fast-Stop (N.O.) Closed: Decelerates at the Fast-Stop time C1-09. To restart the Fast-Stop input must be released and Run must be cycled. 93 17 Fast-stop (N.C.) Open: Decelerates according to C1-09 (Fast-stop Time) 93 20 to 2F External Fault 20: N.O., Always Detected, Ramp To Stop 21: N.C., Always Detected, Ramp To Stop 22: N.O., During Run, Ramp To Stop 23: N.C., During Run, Ramp To Stop 24: N.O., Always Detected, Coast To Stop 25: N.C., Always Detected, Coast To Stop 26: N.O., During Run, Coast To Stop 27: N.C., During Run, Coast To Stop 28: N.O., Always Detected, Fast-stop 29: N.C., Always Detected, Fast-stop 2A: N.O., During Run, Fast-stop 2B: N.C., During Run, Fast-stop 2C:
N.O., Always Detected, Alarm Only (continue running) 2D: N.C., Always Detected, Alarm Only (continue running) 2E: N.O., During Run, Alarm Only (continue running) 2F: N.C., During Run, Alarm Only (continue running) 94 40 Forward Run Command (2-Wire sequence) Open: Stop Closed: Forward run 94