Load Cell Module DVP02LC-SL DVP-PLC Operation Manual 10 CR# Address Attribute Content b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 #22 H’1016 O R/W CH1 unit of measurement Containing max. 4 ASCII words. CR#22, CR#24: for high words CR#23, CR#25: for low words #23 H’1017 O R/W CH1 unit of measurement #24 H’1018 O R/W CH2 unit of measurement #25 H’1019 O R/W CH2 unit of measurement #26 H’101A X R/W Weight correction command For the user to correct the weight. Default: H’0000 H’0001: CH1 reset to zero command H’0002: CH1 weight base point command H’0003: CH2 reset to zero command H’0004:
CH2 weight base point command #33 H’1021 O R/W CH1 weight base point For CR#33 to CR#34, the default value is K1,000 and the range is K-32,768 to K32,767. Steps for correction: (take CH1 for example) 1: Place no weights on the load cell. 2: Set up CR#26 command = H’0001. 3: Place standard weights on the load cell. 4: Write the weight of the weights on the plate into CR#33. 5: Set up CR#26 command = H’0002. #34 H’1022 O R/W CH2 weight base point #35 H’1023 O R CH1 max. weight For setting up the maximum weight. When the measured value exceeds the set value, error codes will be recorded. #36 H’1024 O R CH2 max. weight #37 H’1025 O R/W Upper limit for CH1 zero point check Default: K10; Range:
K-32,768 to K32,767 Reference for reset to zero. When the weight is within the range, the status code will be set to “zero bit”, indicating the current zero weight status. #38 H’1026 O R/W Upper limit for CH2 zero point check #39 H’1027 O R/W Lower limit for CH1 zero point check Default: K-10; Range: K-32,768 to K32,767 Reference for reset to zero. When the weight is within the range, the status code will be set to “zero bit”, indicating the current zero weight status. #40 H’1028 O R/W Lower limit for CH2 zero point check #41 H’1029 X R/W Saving set value (H’5678) Saving the present set value and writing all set values into the internal Flash for use next time when DVP02LC-SL is switched on.
H’0: No action (Default) H’FFFF: Saving is successful H’5678: Writing to internal Flash When H’5678 is written in, all set values will be saved in the Flash. When the saving is completed, CR#41 will become H’FFFF. If the value written in is not H’5678, it will automatically return to H’0, e.g. write K1 into the CR to return it to K0. #43 H’102B X R/W CH1 filter percentage Default: K2 Range: K1 to K5 (Unit: 10%) #44 H’102C X R/W CH2 filter percentage #45 H’102D X R/W CH1 filter average value Displaying the average value after the filtering. Default: K0 Condition to enable the filter: Average times ≥ 30 #46 H’102E X R/W CH2 filter average value