Load Cell Module DVP02LC-SL „ RS-485 Communication y Station address: The node address, corresponding to the value set in CR#54. The range is 1 to 255, and the default setting is 1. y Baud rate: Corresponds to bit4 to bit7 of CR#55. Scroll down to select 9600, 19200, 38400, 57600 or 115200. The default setting is 9600. y Transfer mode: The transmission mode, corresponding to bit15 of CR#55. Scroll down to select RTU or ASCII. The default setting is ASCII. y Data length: Corresponds to bit3 of CR#55. Scroll down to select 7 or 8. The default setting is 7. When the transmission mode is set to be RTU, the data length will be automatically set to 8. y Parity:

Corresponds to bit0 to bit1 of CR#55. Scroll down to select none, odd or even. The default setting is even. y Stop bit: Corresponds to bit2 of CR#55. Scroll down to select 0 or 1. The default setting is 1. 6.3 Parameter Settings The parameter setting window allows you to set up parameters for CH1 and CH2, including displaying the net weight or gross weight, the tare weight, average times, maximum weights, units for measurements, the decimal point place, range and times for standstill checks, zero point checks and filter percentages.

When all the settings are done, click “download” to download the parameters to DVP02LC-SL, or click “Upload” to display the parameters of DVP02LC-SL in the software. DVP-PLC Operation Manual 23