Delta Electronics MS300 — Chapter 3 Installation

Chapter 3 Installation  MS300 (High Speed Model) Chapter 3 Installation Minimum Mounting Clearance and Installation  Prevent fiber particles, scraps of paper, shredded wood saw dust, metal particles, etc. from adhering to the heat sink  Install the AC motor drive in a metal cabinet. When installing one drive below another one, use a metal separation between the AC motor drives to prevent mutual heating and to prevent the risk of  Install the AC motor drive in Pollution Degree 2 environments only: normally only nonconductive accidental fire. pollution occurs and temporary conductivity caused by condensation is expected.

The appearances shown in the following figures are for reference only. Airflow direction: inflow outflow distance Single drive installation Side-by-side horizontal installation Minimum mounting clearance NOTE The minimum mounting clearances A~C stated in the table above applies to AC motor drives installation. Failing to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problems. 3-1 Installation method A (mm) B (mm) C (mm) Ambient temperature (oC) Max. (Without derating) Max. (Derating) Single drive installation 50 30 - 50 60 Side-by-side horizontal installation 50 30 30 50 60 Zero stack installation 50 30 0 40 50