Chapter 5 Main Circuit Terminals MS300 (High Speed Model) 5-2 Main Circuit Terminals It needs following additional terminal when wiring. The additional terminal dimension should comply with the following figure 1. After crimping the wire to the ring lug (must UL approved), UL and CSA approved R/C (YDPU2) heat shrink tubing rated min 600Vac insulation shall be install over the live part. Please refer to the following figure 2. Dimensions of Ring Lug Unit:
mm 5-5 Frame AWG Kit P/N A (MAX) B (MAX) C (MIN) D (MAX) d2 (MIN) E (MIN) F (MIN) W (MAX) t (MAX) B 14 RNBS2-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1 12 RNBS5-4 C 14 RNBS2-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 8.0 1.2 12 RNBS5-4 10 RNBS5-4 8 RNBS8-4 D 12 RNBS5-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 8.0 1.2 10 RNBS5-4 8 RNBS8-4 E 8 RNBS8-5 27.1 6.1 10.5 11.5 5.3 13.0 6.5 12.2 1.7 6 RNB14-5 4 RNBS22-5 F 6 RNBS14-6 35.0 9.0 13.3 14.0 6.2 13.0 19.5 18.0 1.8 4 RNBS22-6 2 RNBS38-6