Chapter 4 Wiring  MS300 After removing the front cover, verify that the power and control terminals are clearly noted. Read the following precautions before wiring. 4-2  Turn off the AC motor drive power before doing any wiring. A charge with hazardous voltages may remain in the DC bus capacitors even after the power has been turned off for a short time. Measure the remaining voltage with a DC voltmeter on +1/DC+ and DC- before doing any wiring. For your safety, do not start wiring before the voltage drops to a safe level (less than 25 V ). Installing wiring with a DC residual voltage may cause personal injury, sparks and a short circuit.

 Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring and commissioning. Make sure the power is turned off before wiring to prevent electric shock.  Make sure that power is only applied to the R/L1, S/L2, and T/L3 terminals. Failure to comply may result in damage to the equipment. The voltage and current must be in the range indicated on the nameplate (refer to Section 1-1 Nameplate Information for details).  All units must be grounded directly to a common ground terminal to prevent damage from a lightning strike or electric shock and reduce noise interference.

 Tighten the screws of the main circuit terminals to prevent sparks caused by screws loosened due to vibration.  For you safety, choose wires that comply with local regulations when wiring.  Check the following items after finishing the wiring: 1. Are all connections correct? 2. Are there any loose wires? 3. Are there any short circuits between the terminals or to ground?