omron — Appendix 1. Specification and Performance Comparison Between CP1E and CP2E

Appendix 1. Specification and Performance Comparison Between CP1E and CP2E ● Functional Specifications 15 Item CP1E E/NS-type CP2E E/S-type CPU Units CP1E N-type CPU Units CP2E N-type CPU Units CPU Units Power supply AC power supply 100 to 240 VAC DC power supply 24 VDC Operation temperature 0°C~55°C -20°C~60°C 0°C~55°C -20°C~60°C Power supply to external devices (service power) Only AC power supply E/N30/40/60S CPU Unit: 300 mA Only AC power supply E/S30/40/60 CPU Unit: 300 mA E14/20 CPU Unit: None Only AC power supply N30/40/60 CPU Unit: 300 mA N14/20 CPU Unit: None Only AC power supply N30/40/60 CPU Unit: 300 mA N14/20 CPU Unit: None High-speed counter inputs ES-type:

Up/down or pulse plus direction inputs: 10 kHz × 2 counters Or Differential phases (4x): 5 kHz × 2 counters Or Increment inputs: 10 kHz × 6 counters 10 kHz × 5 counters (Only for 10 I/O Points) NS-type: Up/down inputs: 100 kHz × 1 counter 10 kHz × 1 counter Or Pulse plus direction inputs: 100 kHz × 2 counters Or Differential phase inputs (4x) 50 kHz × 1 counter 5 kHz × 1 counter Or Incremental pulse inputs 100 kHz × 2 counters 10 kHz × 4 counters Up/down inputs: 100 kHz × 1 counter 10 kHz × 1 counter Or Pulse plus direction inputs:

100 kHz × 2 counters Or Differential phase inputs (4x) 50 kHz × 1 counter 5 kHz × 1 counter Or Incremental pulse inputs 100 kHz × 2 counters 10 kHz × 4 counters Up/down inputs: 100 kHz × 1 counter 10 kHz × 1 counter Or Pulse plus direction inputs: 100 kHz × 2 counters Or Differential phase inputs (4x) 50 kHz × 1 counter 5 kHz × 1 counter Or Incremental pulse inputs 100 kHz × 2 counters 10 kHz × 4 counters N14/20 CPU Unit: Up/down inputs: 100 kHz × 1 counter 10 kHz × 1 counter Or Pulse plus direction inputs: 100 kHz × 2 counters Or Differential phase inputs(4×) 50 kHz × 1 counter 5 kHz × 1 counter Or Incremental pulse inputs 100 kHz × 2 counters 10 kHz × 4 counters N30/40/60 CPU Unit:

Up/down or pulse plus direction inputs: 100 kHz × 2 counters, Or Differential phase inputs(4×) 50 kHz × 2 counters Or Incremental pulse inputs 100 kHz × 3 counters 10 kHz × 3 counters Quick-response / Interrupt inputs 6 inputs 6 inputs 6 inputs 8 inputs (6 inputs only for 14 I/O points) Pulse outputs (Models with transistor outputs only) Pulse output method ES-type: Not supported NS-type: Pulse plus direction only E-type: Not supported S-type: Pulse plus direction only, 2 axes max. Pulse plus direction only 2 axes max. Pulse plus direction only 4 axes max. Speed control ES-type: Not supported NS-type: Supported E-type: Not supported S-type:

Supported Supported Supported Positioning ES-type: Not supported NS-type: Supported E-type: Not supported S-type: Supported Supported Supported Origin searches ES-type: Not supported NS-type: Supported E-type: Not supported S-type: Supported Supported Supported PWM outputs (Models with transistor outputs only) ES-type: Not supported NS-type: 1 output E-type: Not supported S-type: 1 output 1 output 1 output Analog I/O Not supported Not supported Supported (Only for NA20) Not supported Analog volume Not supported Not supported Supported Not supported USB port Provided.

USB2.0 Full-speed (12M) Not provided Ethernet port Not provided Provided With switch function* * N14/20 is not supported. Built-in serial communication port ES-type: Not provided NS-type: RS-232C NS1-type: RS-232C and RS-485 Provided. E-type: RS-232C S-type: RS-232C and RS-485 Provided. N-type: RS-232C Not provided Provided by installing Option Board. Serial option board Not provided N14/20 CPU Unit: None N30/40/60 CPU Unit: 1 slot N14/20 CPU Unit: 1 slot N30/40/60 CPU Unit:

2 slots Serial communi- cation protocols Baud rate 1200/2400/4800/9600/19.2k/38.4k/57.6k/115.2k Supported protocol • Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU easy master • Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master • Modbus-RTU Slave • Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU easy master • Host Link* • 1:N NT Link* • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master • Modbus-RTU Slave * PORT1 (EX) is not supported.