SAMI G S 8.3 Installation Inspection Inspect the mechanical and electrical instal- lation of the SAMI for compliance with the prevailing electrical installation regulations and the installation instructions contained in Sections 4 - 6. A LANGUAGE in Setting mode. A LANGUAGE Select the preferred language. Press to confirm the selection and move to the next parameter. Note! Ensure the motor cable is discon- nected before proceeding with the Keypad control test without motor (see page 32). B APPLICATIONS Refer to the Application Macro Manual for complete information concerning the Ap- plication Macros. Select the Application Macro which best corresponds to your appli- cation.
The parameter settings in each Macro can be set separately to adapt to your application. Press to move to the next parameter. Ensure the following is inspected: - protective earthing of the SAMI and the motor - supply and motor cables (cable cross section, fuse protection, connections, cable screen earthing; see Table 5-1, 5-2 and Figure 5-2, 5-3 on pages 16 and 18) C APPLIC. RESTORE - control cables (connections, cable screen earthing, location as far as possible from the power cables); for analogue input signal selection, see Figure 6-1 This parameter allows you to retrieve the factory settings of the selected Application Macro. Press to move to the next parameter.
- quantity and quality of cooling air for the SAMI, see section 4.1 D SUPPLY VOLTAGE ( U N ) E POLE NUMBER - check that the on/off switches of all external controls (if existing) are set to off. Make sure that starting of the motor is allowed. F MOTOR NOM CURRENT ( I M ) G MOTOR NOM POWER ( P M ) - connect the SAMI to the mains. Check by measurement that the voltage between U1-V1, U1-W1 and V1-W1 is U N + 10 %. H COS PHI OF MOTOR Set the correct values corresponding to the supply network and the driven motor. Press to move to the next parameter. 8.4 Start-Up Data Parameters Power up the SAMI. The display shows Operating Data parameter 1, SAMI OUTPUT FREQ at the first power up.
Before proceed- ing with the commissioning, check and complete the Start-Up Data parameter values. When you have scrolled through all the parameters A-H and pressed after setting the parameter H COS PHI OF MO- TOR, the display shows again Operating Data parameter 1 SAMI OUTPUT FREQ. Note! If the nominal current of the motor is different from the nominal current of the SAMI GS, set parameter 27.3 MOTOR POWER accordingly (refer to page 57). While viewing para. 1, SAMI OUTPUT FREQ, first press and hold, then press .The display shows parameter 31