User Manual EM303B General Purpose Inverter inverter to restart from fault output stop to auto-reset. The range is 0.01 ~ 30.00 seconds and can be set continuously. FC-25 is for controlling the time for inverter to reset fault retry times. Fault occurs in running process. After reset and restart, inverter will record the times of fault reset which have been done. If there is no fault in the setting time of FC-25, inverter will clear the fault retry times automatically. No fault timelag is in the range of 0.01 ~ 30.00 seconds and can be set continuously. Setting the running mode at restart The function is controlled by F0-19. 8.13.20 Fault Type Options Fault retry control is bit operation.

Only the corresponding bit has to be set as 0 or 1. As shown in the table below. For instance: SOU and OL fault retry is permitted, and the other faults retries are prohibited. Only the Bit 3 corresponding to SOU and Bit 6 corresponding to OL have to be set as 0, the other bits are set as 1, i.e. FC-27=10110111. 8.13.21 Setting Disabled Trips Bit setting value=0 After detecting the fault corresponding to the bit, inverter will stop and enter fault status. Bit setting value=1 After detecting the fault corresponding to the bit, inverter will output 154 No. Function Range Unit Default Type Fault Retry Options * Ol IlP SlU SOU SOC HOU HOC 11111111 〇 1 1 1 1 1 1 1 1 FC-27 0:

Fault retry permitted 1: Fault retry prohibited *: Not used Fault Code * Ol IlP SlU SOU SOC HOU HOC Bit * 6 5 4 3 2 1 0 Value * 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Functio Uni Default Typ No. Range n t e Disabled Trips 1 Ol IlP SlU SOU SOC * * * 0000000 0 〇 FC-28 0 0 0 0 0 0 0 0 0: Enabled 1: Disabled *:Not Used Disabled Trips 2 EEd EST * * * EHT OlP OH 0000001 0 〇 FC-29 0 0 0 0 0 0 1 0 0: Enabled 1: Disabled *:Not Used Disabled Trips 3 * Ol1 SOFT SIE SrE SFE STP EEU 0000000 0 〇 FC-30 0 0 0 0 0 0 0 0 0: Enabled 1: Disabled *:Not Used