Ethernet Communication Module IFD9506 PC Master Ethernet RS-485 (Slave Mode) AC motor driver 4 Registers in IFD9506 4.1 Basic Registers (BR) DVP-PLC Application Manual 8 S-485 (Master Mode) RS-485 (Master Mode) R Hum r Temperature mac controller interf BR# Attribute Content Explanation Default Latched 0 R Model name Set up by the system; read only. The model code of IFD9506 = H’0200 Yes 1 R Firmware vers Displaying the current firmwawre version in hex, ion e.g. V1.2 is indicated as high byte = 0x01 and low byte = 0x20. Yes 2 R Release data the version Displaying the data in decimal form. 10,000s digit and 1,000s digit are for “month”; 100s digit and 10s of digit are for “day”. For 1s digit:
0 = morning; 1 = afternoon. Example: 12191 indicates the version released in the afternoon of December 19. Yes 3 Reserved 4 R/W Communicatio format n Please refer to the table of communication format setting. No 5 R/W Baud rate Please refer to the table of baud rate setting. No 6 R/W Address For setting up the station address No 7 R Number of DI/ points DO DI: high bytes; DO: low bytes 0x300 Yes 8 Reserved 9 R Error code Displaying the errors. Please refer to the table of error codes. 0 No 10 Reserved 11 R/W Communicatio time-out n For setting up the communication time-out (ms) in Modbus TCP mode.
5,000 Yes 12 R/W Communicatio delay time n For setting up the minimum interval time between every communication datum.。 0 Yes 13 R/W TCP connectio idle time n For setting up idle time for TCP communication Unit: second 30 Yes