Load Cell - Single Belt Scale Installation Where separation between the BW100 and belt scale exceeds 150 m (500 ft.): 1. remove the jumpers BW100 TB1 – 17/18 and TB1 19/20 2. run additional conductors from: BW100 TB1 – 18 to scale ‘– EXC’ BW100 TB1 – 19 to scale ‘+ EXC’ If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens Milltronics. 7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 9 + + S S E E I I X X G G C C s h g w r b l r h e l d n t d k BW100 TB1 UPPER SIG B customer + SIG B junction box LOADCELL SIG A + SIG A CNST. SPD. BW100 TB1 LOWER EXC * SEN Note: If load cells are supplied with LOADCELL sense wiring:
+ SEN terminate brown with black = T17 * + EXC and blue with red = T20 at junction box SHIELD S I G w h t + E X C r e d E X C b l k