DeviceNet Slave Communication Module IFD9502 z Note The changed setting of communication mode is only valid when IFD9502 is re-powered. When IFD9502 is operating, changing the setting of communication mode will be invalid. 3. Setting up baud rate z Note: The changed setting of the baud rate of DeviceNet is only valid when IFD9502 is re-powered. When IFD9502 is operating, changing the baud rate will be invalid.

2.5 Communication ports on IFD9502 The communication ports on IFD9502 are used for the connection with the equipment (Delta programmable logic controller, Delta AC motor PORT1 PORT2 drive, Delta temperature controller, Delta servo drive, Delta human machine interface and custom equipment). 1. PORT 1 PIN definition z Note: PORT 1 supports RS-485 communication only. 2. PORT 2 PIN definition z Note PORT 2 supports RS-232 and RS-485 communication only. DVP-PLC Application Manual 6 PIN 8 PIN 7 PIN 6 Baud rate of slave device Reserved Off Off 125k bps Off On 250k bps On Off 500k bps On On Auto baud rate detection PORT 1 sketch PIN Description 6 5 4 3 2 1 PORT1 1 N.C. 2 GND 3 DATA- 4 DATA+ 5 N.C.

6 N.C. PORT 2 sketch PIN RS-232 RS-485 1 6 2 7 3 8 4 9 5 DB9 male 1 N.C. N.C. 2 RXD N.C. 3 TXD DATA- 4 N.C. N.C. 5 GND N.C. 6 N.C. N.C. 7 N.C. N.C. 8 N.C. DATA+ 9 N.C. N.C.