Single-axis controllers General data and operating conditions 4 4.2 EMC Operation on public supply systems EN 61800-3 The controllers are designed for use in an industrial environment. Operation on public networks requires measures to be taken for limiting the expected emission of radio interferences. Noise emission, in cables Design ”Single Drive” EN 61800-3 see Tab. 4.2-2 EMC protection requirements Design ”Multi Drive” Depending on the filter at the central DC supply module. Noise immunity (to EN 61800-3) Electrostatic discharge (ESD) EN 61000-4-2 8 kV with air discharge, 4 kV with contact discharge against housing Radio frequency Cable-guided EN 61000-4-6 150 kHz ...
80 MHz, 10 V/m 80 % AM (1 kHz) Interference (housing) EN 61000-4-3 80 MHz ... 1000 MHz, 10 V/m 80 % AM (1 kHz) Burst Power terminals and interfaces EN 61000-4-4 2 kV/5 kHz Signal interfaces EN 61000-4-4 1 kV/5 kHz Control connections EN 61000-4-4 2 kV/5 kHz Surge (surge voltage) Power terminals EN 61000-4-5 1.2/50 μ s, 1 kV phase/phase, 2 kV phase/PE 4.2-4 EDS94SPP101 EN 3.1-04/2007