User Manual of A90 Series Inverter 7.2 Motor 1 parameter group of F01 group The A90 series inverter supports asynchronous and synchronous motors. Please set this parameter correctly according to the actual situation. The above function codes are the nameplate parameters of the asynchronous motor. When the motor is connected to the inverter for the first time, regardless of VF control or vector control, the above parameters must be correctly set according to the motor nameplate before operation. When the rated power (F01.01) of the motor is changed, the values of F01.03 to F01.08 of the inverter will change automatically. Pay attention to this during operation.

132 Function Default Function code name Parameter description Unit Attribute code setting F01.00 Motor type 0: ordinary asynchronous motor 1: variable-frequency asynchronous motor 2: permanent magnet synchronous motor 0 ○ Function Function code Parameter description Unit Default setting Attribute code name F01.01 Rated power of electric motor 0.10~650.00 kW Depending on the motor type ○ F01.02 Rated voltage of motor 50~2000 V Depending on the motor type ○ F01.03 Rated current of motor 0.01 ~ 600.00 (rated power of motor: ≤ 75 kW) 0.1 ~ 6000.0 (rated power of motor:

> 75 kW) A Depending on the motor type ○ F01.04 Rated frequency of motor 0.01~600.00 Hz Depending on the motor type ○ F01.05 Rated speed 1~60000 rpm Depending on the motor type ○ F01.06 Motor winding connection 0: Y 1: Δ Depending on the motor type ○ F01.07 Rated power factor of motor 0.600~1.000 Depending on the motor type ○ F01.08 Motor efficiency 30.0~100.0 % Depending on the motor type ○