User Manual of A90 Series Inverter The function codes F01.09 to F01.13 are the parameters of the asynchronous motor. They are usually unavailable to users. Please get them through motor parameter self-identification (F01.34). When the motor parameters (F01.01 to F01.08) are modified, the values of F01.09 to F01.13 of the inverter will change automatically. Pay attention to this during operation. Before the motor parameter self-identification, be sure to set F01.00 to F01.08 correctly according to the actual situation. The specific meanings of motor parameters are shown in Fig. 7-6:

133 Function Function code Default Parameter description Unit Attribute code name setting F01.09 Stator resistance of asynchronous motor 1~60,000 (rated power of motor: ≤ 75 kW) 0.1~6,000.0 (rated power of motor: > 75kW) mΩ Depending on the motor type ○ F01.10 Rotor resistance of asynchronous motor 1~60,000 (rated power of motor: ≤ 75 kW) 0.1~6,000.0 (rated power of motor: > 75kW) mΩ Depending on the motor type ○ F01.11 Leakage inductance of asynchronous motor 0.01 ~ 600.00 (rated power of motor: ≤ 75 kW) 0.001~ 60.000 (rated power of motor: > 75 kW) mH Depending on the motor type ○ F01.12 Mutual inductance of asynchronous motor 0.1 ~ 6,000.0 (rated power of motor:

≤ 75 kW) 0.01 ~ 600.00 (rated power of motor: > 75 kW) mH Depending on the motor type ○ F01.13 No-load excitation current of asynchronous motor 0.01 ~ 600.00 (rated power of motor: ≤ 75 kW) 0.1 ~ 6,000.0 (rated power of motor: > 75 kW) A Depending on the motor type ○