User Manual of A90 Series Inverter ★ Fmax, maximum frequency (F00.16) Ie, rated current of the inverter (F12.21) Ue, rated voltage of the inverter (F12.20) Pe, rated power of the inverter (F12.19) the voltage signal (0.00V to 10.00V) and current signal (0.00mA to 20.00mA) via the DIP The output physical quantity of the analog output terminal can be switched between switch. For the voltage signal output, the value from 0.0% to 100.0% corresponds to the output 0.00V to 10.00V. For the current signal output, the value from 0.0% to 100.0% corresponds to the output 0.00mA to 20.00mA. For details, please see “0 Wiring of analog output terminals”.
The above function codes are usually used to correct the zero drift of analog output and the deviation of output amplitude. They can also be used to customize the required AO output curve to meet the requirements of different instruments or others. If the offset is represented by “b”, the gain by “k”, actual output by “Y” and standard output by “X”, the actual output is: Y=kX+b. 1. In order to meet the needs of different instruments or external devices, the full-scale voltage of M1 and M2 is actually 10.9V and the full-scale current is actually 22mA. 2. M1 and M2 are set to 0.00-10.00V by default. 3.
Where there are high precision requirements for the analog output during operation, test the no-load outputs of the terminals M1 and M2 with a multimeter first. 160 29 Acceleration an deceleration outpu frequency d t Function Function code Default Parameter description Unit Attribute code name setting F03.27 M1 output bias -100.0 - 100.0 % 0.0 ● F03.28 M1 output gain -10.00 - 10.00 1.00 ● F03.29 M2 output bias -100.0 - 100.0 % 0.0 ● F03.30 M2 output gain -10.00 - 10.00 1.00 ● Function Default Function code name Parameter description Unit Attribute code setting F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 * * * * * 00000 ●