User Manual of A90 Series Inverter 159 100.0% 6 Bus voltage 0V to about 2.63*Ue, corresponding to the output 0.0% to 100.0% (That is, for the 220V driver, 579V corresponds to the output 100.0%; and for the 380V driver, 1000V corresponds to the output 100.0%. Drivers at different voltage levels have the same output voltage at their rated voltages.) 7 Output power 0.00kW to 2*Pe, corresponding to the output 0.0% to 100.0% 8 AI1 Output the actual input voltage, instead of the offset result.
0.0% to 100.0%, corresponding to the output 0.0% to 100.0% 9 AI2 13 Reserved 14 Count value 0 to F16.03, corresponding to the output F16.10 to F16.11 15 Length value 0 to F16.01, corresponding to the output F16.10 to F16.11 16 PID output percentage -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% 18 PID feedback -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% 19 PID setting -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% 21 Output frequency (actual value) 22 Set frequency (actual value) 23 Output current (actual value) 24 Output torque (actual value) 25 Set torque (actual value) 26 Estimated feedback frequency (actual value) 27 Synchronization frequency (actual value)