sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter stall fault. When the continuous stall time exceeds the set value of F07.28, the driver will report a In the stall status, the driver will perform automatic control according to the set value of F07.29. The intensity setting depends on the on-site application, instead of maximization. 7.9 Multi-segment Speed and Simple PLC Parameter Group of F08 Group 188 Default Function code Function code name Parameter description Unit Attribute setting F07.28 Stall fault detection time 0.0-6000.0 (0.0:

no stall fault detection) s 0.0 ○ F07.29 Stall control intensity 0 - 100 % 100 ○ Function Function code Default Parameter description Unit Attribute code name setting F08.00 Multi-segment speed 1 0.00 to maximum frequency F00.16 Hz 0.00 ● F08.01 Multi-segment speed 2 0.00 to maximum frequency F00.16 Hz 5.00 ● F08.02 Multi-segment speed 3 0.00 to maximum frequency F00.16 Hz 10.00 ● F08.03 Multi-segment speed 4 0.00 to maximum frequency F00.16 Hz 15.00 ● F08.04 Multi-segment speed 5 0.00 to maximum frequency F00.16 Hz 20.00 ● F08.05 Multi-segment speed 6 0.00 to maximum frequency F00.16 Hz 25.00 ● F08.06 Multi-segment speed 7 0.00 to maximum frequency F00.16 Hz 30.00 ● F08.07 Multi-segment speed 8 0.00 to maximum frequency F00.16 Hz 35.00 ● F08.08 Multi-segment speed 9 0.00 to maximum frequency F00.16 Hz 40.00 ● F08.09 Multi- speed 10 0.00 to maximum frequency F00.16 Hz 45.00 ● F08.10 Multi-segment speed 11 0.00 to maximum frequency F00.16 Hz 50.00 ● F08.11 Multi-segment speed 12 0.00 to maximum frequency F00.16 Hz 50.00 ●