User Manual of A90 Series Inverter 76 1 0: level 1: single pulse F03.06 Positive/negative logic of digital output D7 D6 D5 D4 D3 D2 D1 D 0 00000 ○ * * * * * R1 * Y1 0: positive logic is valid in the closed state/invalid in the open state 1: negative logic is valid in the closed state/invalid in the open state F03.08 Output status control in jog D7 D6 D5 D4 D3 D2 D1 D 0 00000 ○ * * * RE V FD T2 FD T1 FA R R U N 0: valid in jogging 1:

invalid in jogging F03.09 Y1 valid delay time 0.000~30.000 s 0.000 ● F03.10 Y1 invalid delay time 0.000~30.000 s 0.000 ● F03.13 R1 valid delay time 0.000~30.000 s 0.000 ● F03.14 R1 invalid delay time 0.000~30.000 s 0.000 ● F03.17 Single pulse time of Y1 output 0.001~30.000 s 0.250 ● F03.19 Single pulse time of R1 output 0.001~30.000 s 0.250 ● F03.21 Options of analog output M1 0: running frequency (absolute value) 1: set frequency (absolute value) 2: output torque (absolute value) 3: set torque (absolute value) 4: output current 5: Output voltage 6: bus voltage 7: output power 8: AI1 9: AI2 11: VP 13: Communication setting 14: count value 0 ○ F03.22 Options of analog output M2 2 ○