User Manual of A90 Series Inverter 77 15: length value 16: PID output percentage 18: PID feedback 19: PID setting 21: output frequency (actual value) 22: set frequency (actual value) 23: output current (actual value) 24: output torque (actual value) 25: set torque (actual value) 27: estimated feedback frequency (actual value) 28: synchronization frequency (actual value) 29:
acceleration and deceleration output frequency (actual value) F03.27 M1 output bias -100.0~100.0 % 0.0 ● F03.28 M1 output gain -10.00~10.00 1.00 ● F03.29 M2 output bias -100.0~100.0 % 0.0 ● F03.30 M2 output gain -10.00~10.00 1.00 ● F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 * * * * * R1 * Y1 0: no output 1: output 00000 ● F04 Start/stop control parameter group F04.00 Start-up method 0: direct start 1:
start of speed tracking 0 ○ F04.01 Start frequency 0.00~10.00 Hz 0.00 ○ F04.02 Start frequency hold time 0.00-60.00, 0.00 is invalid s 0.00 ○ F04.03 Starting current of DC braking 0.0~100.0 (100.0 = Rated current of motor) % 50.0 ○ F04.04 Starting time of DC braking 0.00~30.00 s 0.00 ○ F04.05 Reserved F04.06 Pre-excitation current 50.0-500.0 (100.0 = no-load current) % 100.0 ○ F04.07 Pre-excitation time 0.00~10.00 s 0.10 ○ F04.08 Speed tracking mode Ones place: Tracking start frequency 0: maximum frequency 0 1 ○