sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter 84 synchronous motor F06.48 Filtering time constant of speed tracking of synchronous motor 0.00~10.00 ms 0.40 ○ F06.49 Speed tracking control intensity of synchronous motor 1.0~100.0 5.0 ○ F06.50 Speed tracking control threshold of synchronous motor 0.00~10.00 0.20 ○ F06.51 Injection current (Iq) rise time of synchronous motor 0.010~1.000 S 5.0 F07 Protection function setting group F07.00 Protection shield E20 E22 E13 E06 E05 E04 E0 7 E08 000 00000 ○ 0: valid protection 1: shielded protection F07.01 Motor overload protection gain 0.20~10.00 1.00 ● F07.02 Motor overload pre-alarm coefficient 50~100 % 80 ● F07.06 Bus voltage control options Ones place:

Instantaneous stop/no-stop function options 0: Invalid 1: deceleration 2: deceleration to stop Tens place: Overvoltage stall function options 0: Invalid 1: valid 10 ○ F07.07 Voltage of overvoltage stall control 110.0~150.0 (380V,100.0=537V) % 131.0 (703V) ○ F07.08 Instantaneous stop/no-stop operating voltage 60.0 to instantaneous stop/no-stop recovery voltage (100.0 = standard bus voltage) % 76.0 ○ F07.09 Instantaneous stop/no-stop recovery voltage Instantaneous stop/no-stop operating voltage to 100.0 % 86.0 ● F07.10 Check time for instantaneous 0.00-100.00 s 0.50 ●