sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter 85 stop/no-stop recovery voltage F07.11 Current limit control 0: Invalid 1: limit mode 1 2: limit mode 2 2 ○ F07.12 Current limit level 20.0-180.0(100.0 = the rated current of inverter) % 150.0 ● F07.13 Quick current limit options 0: Invalid 1: valid 0 ○ F07.14 Number of retries after failure 0-20; 0: disable retry after failure 0 ○ F07.15 Options of digital output action in retries after failure 0: no action 1: action 0 ○ F07.16 Interval of retries after failure 0.01~30.00 s 0.50 ● F07.17 Restoration time in retries after failure 0.01~30.00 s 10.00 ● F07.18 Options of retries after failure E07 E03 E02 E06 E05 E0 4 **0 00000 ○ 0:

allow retry after failure 1: disable retry after failure F07.19 Action option 1 after failure E21 E16 E15 E14 E13 E12 E08 E07 000 00000 ○ 0: free stop 1: stop according to stop mode F07.20 Action option 2 after failure E28 E27 E25 E23 *0000 ○ 0: free stop 1: stop according to stop mode F07.21 Options of load loss protection 0: invalid 1: valid 0 ● F07.22 Load loss detection level 0.0~100.0 % 20.0 ● F07.23 Load loss detection time 0.0~60.0 s 1.0 ● F07.24 Options of load loss protection action 0: free stop 1: stop according to stop mode 1 ○ F07.25 ~F07.2 6 Reserved F07.27 AVR function 0: Invalid 1: valid 2: automatic 1 ○