User Manual of A90 Series Inverter 93 fifteenth segment min F09 PID function group F09.00 PID setting source 0: digital PID setting 1: AI1 2: AI2 3: retention 4:VP 5: retention 6: communication setting (percentage setting) 0 ○ F09.01 Digital PID setting 0.0 to PID setting feedback range F09.03 0.0 ● F09.02 PID feedback source 1: AI1 2: AI2 3-5: retention 6: communication setting (percentage setting) 1 ○ F09.03 PID setting feedback range 0.1~6,000.0 100.0 ● F09.04 PID positive and negative action selection 0: positive 1: negative 0 ○ F09.05 Proportional gain 1 0.00-100.00 0.40 ● F09.06 Integral time 1 0.000-30.000, 0.000:

no integral s 10.000 ● F09.07 Differential time 1 0.000-30.000 ms 0.000 ● F09.08 Proportional gain 2 0.00-100.00 0.40 ● F09.09 Integral time 2 0.000-30.000, 0.000: no integral s 10.000 ● F09.10 Differential time 2 0.000-30.000 ms 0.000 ● F09.11 PID parameter switching conditions 0: no switching 1: switching via digital input terminal 2: automatic switching according to deviation 0 ● F09.12 PID parameter switching deviation 1 0.00 - F09.13 % 20.00 ● F09.13 PID parameter switching deviation 2 F09.12 - 100.00 % 80.00 ● F09.14 Initial PID value 0.00-100.00 % 0.00 ● F09.15 PID initial value holding time 0.00~650.00 s 0.00 ● F09.16 Upper limit of PID output F09.17 - +100.0 % 100.0 ●