User Manual of A90 Series Inverter 94 F09.17 Lower limit of PID output –100.0 - F09.16 % 0.0 ● F09.18 PID deviation limit 0.00-100.00 (0.00:
invalid) % 0.00 ● F09.19 PID differential limit 0.00-100.00 % 5.00 ● F09.20 PID integral separation threshold 0.00-100.00 (100.00% = invalid integral separation) % 100.00 ● F09.21 PID setting change time 0.000-30.000 s 0.000 ● F09.22 PID feedback filtering time 0.000-30.000 s 0.000 ● F09.23 PID output filtering time 0.000-30.000 s 0.000 ● F09.24 Upper limit detection value of PID feedback disconnection 0.00-100.00; 100.00 = invalid feedback disconnection % 100.00 ● F09.25 Lower limit detection value of PID feedback disconnection 0.00-100.00; 0.00 = invalid feedback disconnection % 0.00 ● F09.26 Detection time of PID feedback disconnection 0.000-30.000 s 0.000 ● F09.27 PID sleep control options 0:
Invalid 1: sleep at zero speed 2: sleep at lower frequency limit 3:
sleep with tube sealed 0 ● F09.29 Sleep delay time 0.0 - 6500.0 s 0.0 ● F09.30 Wake-up action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 0.00 ● F09.31 Wake-up delay time 0.0~6,500.0 s 0.0 ● F09.32 Multi-segment PID setting 1 0.0 to PID setting feedback range F09.03 0.0 ● F09.33 Multi-segment PID setting 2 0.0 to PID setting feedback range F09.03 0.0 ● F09.34 Multi-segment PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 90.0 ● F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 bar 6.0 ● F09.42 Overpressure 0-3,600 (0: invalid) S 3 ●