Chapter 9 Troubleshooting 9.3.5. Others 9_ 9-53 Error Code Description Corrective action 16#000F The original program in the PLC is damaged. After users compile the program again, they can download the program again. 16#0024 There is no IO module on the backplane. Check whether the IO module is on the backplane. 16#005E The memory card is initialized incorrectly. (SM453) Check whether the memory card breaks down. 16#005F The file to be read does not exist in the memory card; or the file directory to write in a file does not exist. (SM453) Check whether the file name and file directory is correct. 16#0061 The storage capacity of the memory card is not enough.
(SM453) Check whether the storage capacity of the memory card is enough, or whether the memory card breaks down. 16#0062 The memory card is write-protected. (SM453) Check whether the memory card is write-protected. 16#0063 An error occurs when the data is written into the memory card. (SM453) Check whether the file path is correct, or whether the memory card breaks down. 16#0064 The file in the memory card can not be read. (SM453) Check whether the file path is correct, or whether the file is damaged. 16#0065 The file in the memory card is a read-only file. (SM453) Users need to set the file so that the file is not a read-only file.
16#1801 There is no interrupt service routine in the CPU module. Check whether a corresponding interrupt service routine is created in the PLC program (24V LV Detection) 16#3400 Axis setting error (1~32) Cause: motion axis number is not between 1 and 32 Action: set the axis number between 1 and 32 and re-execute the function block 16#3401 SDO DataType setting error (0~199) Cause: data type cannot be matched with the object library Action: confirm the object library of the slave station 16#3404 The number of the channel exceeds the available setting range Cause: the input channel exceeds the setting range Action:
set up the channel number for input again and re-execute the function block 16#3414 Pulse type counter setting error Cause: the pulse type range is set other than 0~3 Action: set up the pulse type range and re-execute the function block 16#3415 Comparison condition setting error Cause: the comparison condition is set other than 0~2 Action: set up the comparison condition again and re-execute the function block 16#3429 Gcode format error Cause: G code file contains unsupported G code or the format is wrong Action: check the G code file contents and replace the unsupported G code with a supported one or fix the G code format. After that re-download the G code file.